Specification | Value |
---|---|
Nominal Voltage (4 x 3.7v) | 14.8v |
Max Voltage (4 x 4.2v) | 16.8v |
Min Voltage (4 x 3.0v) | 12.0v |
Cells in Series for Voltage | 4 |
Parallel Cells to Get Capacity 40Ah/2.0Ah | 20 |
Total Cells Required | 80 |
Battery Management System
3S 100A Li-ion Lithium 18650 BMS Battery Charger Protection Board with Balance
Feature | Details |
---|---|
Large discharge current | 100A |
Instantaneous discharge current | 150A |
Charging voltage | 12.6V |
Large charge current | 10A |
Overcharge detection voltage | 4.28±0.05V |
Overcharge protection delay | 0.5S |
Overcharge release voltage | 4.08±0.1V |
Power balance detection voltage | 4.20±0.05V |
Power balance release voltage | 4.20±0.05V |
Electricity balance current | 42±5mA |
Over discharge detection voltage | 2.8±0.1V |
Overdischarge detection delay | 0.1S |
Over discharge release voltage | 3.0±0.1V |
Overcurrent detection voltage | 150mV |
Overcurrent detection delay | 9mS |
Overcurrent protection current | 200±10A |
Overcurrent protection release condition | Disconnect the load |
Short circuit protection conditions | External load short circuit |
Short circuit detection delay | 250uS |
Main circuit conduction resistance | ≤25mΩ |
Working current | ≤20uA |
Sleep current (when battery is over) | ≤10uA |
Size | 8.2x5.1cm/3.23x2.01inch |
Test Results of Batteries
...