Configure Remote UPS using APCUPSD


Edit the configuration

Code Block
$ sudo vi /etc/apcupsd/apcupsd.conf


Set the following values

Code Block
UPSCABLE ether
UPSTYPE net
#DEVICE <masterIP>:<port>
DEVICE 192.168.1.50:3551
 
# If during a power failure, the remaining battery percentage
# (as reported by the UPS) is below or equal to BATTERYLEVEL,
# apcupsd will initiate a system shutdown.
BATTERYLEVEL 50
 
# If during a power failure, the remaining runtime in minutes
# (as calculated internally by the UPS) is below or equal to MINUTES,
# apcupsd, will initiate a system shutdown.
MINUTES 10

...

Start apcupsd

Code Block
$ apcupsd


Test local configuration

Code Block
$ apcaccess status
 
APC      : 001,036,0917
DATE     : 2021-08-23 16:05:50 -0400 
HOSTNAME : nas0
VERSION  : 3.14.10 (13 September 2011) debian
UPSNAME  : MehanUPS
CABLE    : Ethernet Link
DRIVER   : Back-UPS ES 750
UPSMODE  : Stand Alone
STARTTIME: 2021-08-23 16:01:50 -0400 
MASTERUPD: 2021-08-23 16:05:50 -0400 
MASTER   : 192.168.1.50:3551
STATUS   : ONLINE SLAVE
LINEV    : 121.0 Volts
LOADPCT  :  13.0 Percent Load Capacity
BCHARGE  : 100.0 Percent
TIMELEFT :  13.6 Minutes
MBATTCHG : 0 Percent
MINTIMEL : 3 Minutes
MAXTIME  : 0 Seconds
SENSE    : Medium
LOTRANS  : 092.0 Volts
HITRANS  : 139.0 Volts
BATTV    : 13.6 Volts
LASTXFER : Low line voltage
NUMXFERS : 0
TONBATT  : 0 seconds
CUMONBATT: 0 seconds
XOFFBATT : N/A
SELFTEST : NO
STATFLAG : 0x07000408 Status Flag
SERIALNO : 5B1036T73179
BATTDATE : 2010-09-05
NOMINV   : 120 Volts
NOMBATTV :  12.0 Volts
NOMPOWER : 450 Watts
FIRMWARE : 841.I3 .D USB FW:I3
END APC  : 2021-08-23 16:06:39 -0400

...