Overview

The objective is to supply power to the house for critical systems in the event of a power outage. We have 2.4 kW of lithium battery power and multiple inverters. Ideally, we would like to group our batteries and connect the inverter directly to the panel and select what circuits we need to power. We will be supplying only 120VAC to only 1 phase.

Inverter Connect Directly to Appliance

Here is an example of what we used initially. Just a battery and inverter independently powering our espresso machine.

Image Added


Renogy Pure Since Inverter

The inverter we are using is a Renogy 3000W pure sine inverter. This inverter has ground and neutral bonded together inside the inverter. This is good when installed in a RV but won't work when tying it to your panel. 


In order to get this to work when connected to our house, we will leave the ground disconnected.


The thought here is that the ground is supplied by the house which will protect our connected devices. This however may mean that the case of our inverter has a floating ground. Not sure if this is a concern or not. In the event of shock from the case, the GFCI in the inverter should trip making things safe.



Image AddedImage Added


Panel Rework


We moved around some circuits in the panel to ensure all critical circuits are on the same phase.  


Image Added


Connecting to the Panel

...