To connect our inverter to the panel, we simply connected our inverter to a receptacle which was running on the desired phase (L2 in our case). Ideally, this receptacle should not be on a circuit containing a GFCI or arc fault breaker. It will still work but if the GFCI/Arc Fault trips, you won't be able to reset the circuit.



Connection Steps to Follow

  • turn off the input cuircuit on panel! (main power)
  • turn off all circuits
  • connect inverter to receptacle on desired phase. (Ideally a circuit not protected by a GFCI or arc fault breaker)
  • power on inverter
  • turn on critical circuits on panel.

...