Verify that your changes are saved by verifying in the UI
Configure Remote UPS using APCUPSD
Edit the configuration
Code Block |
---|
$ sudo vi /etc/apcupsd/apcupsd.conf |
Set the following values
Code Block |
---|
UPSCABLE ether
UPSTYPE net
#DEVICE <masterIP>:<port>
DEVICE 192.168.1.50:3551
# If during a power failure, the remaining battery percentage
# (as reported by the UPS) is below or equal to BATTERYLEVEL,
# apcupsd will initiate a system shutdown.
BATTERYLEVEL 50
# If during a power failure, the remaining runtime in minutes
# (as calculated internally by the UPS) is below or equal to MINUTES,
# apcupsd, will initiate a system shutdown.
MINUTES 10 |
Start apcupsd
Code Block |
---|
$ apcupsd |
Test local configuration
Code Block |
---|
$ apcaccess status
APC : 001,036,0917
DATE : 2021-08-23 16:05:50 -0400
HOSTNAME : nas0
VERSION : 3.14.10 (13 September 2011) debian
UPSNAME : MehanUPS
CABLE : Ethernet Link
DRIVER : Back-UPS ES 750
UPSMODE : Stand Alone
STARTTIME: 2021-08-23 16:01:50 -0400
MASTERUPD: 2021-08-23 16:05:50 -0400
MASTER : 192.168.1.50:3551
STATUS : ONLINE SLAVE
LINEV : 121.0 Volts
LOADPCT : 13.0 Percent Load Capacity
BCHARGE : 100.0 Percent
TIMELEFT : 13.6 Minutes
MBATTCHG : 0 Percent
MINTIMEL : 3 Minutes
MAXTIME : 0 Seconds
SENSE : Medium
LOTRANS : 092.0 Volts
HITRANS : 139.0 Volts
BATTV : 13.6 Volts
LASTXFER : Low line voltage
NUMXFERS : 0
TONBATT : 0 seconds
CUMONBATT: 0 seconds
XOFFBATT : N/A
SELFTEST : NO
STATFLAG : 0x07000408 Status Flag
SERIALNO : 5B1036T73179
BATTDATE : 2010-09-05
NOMINV : 120 Volts
NOMBATTV : 12.0 Volts
NOMPOWER : 450 Watts
FIRMWARE : 841.I3 .D USB FW:I3
END APC : 2021-08-23 16:06:39 -0400 |
Set APCUPSD to start at bootup
Mount the flash
Code Block |
---|
$ /etc/init.d/init_disk.sh mount_flash_config |
Edit the autorun.sh script
Code Block |
---|
$ vi /tmp/nasconfig_tmp/autorun.sh |
Add apcupsd to run
Code Block |
---|
/sbin/apcupsd |
Unmount the flash
Code Block |
---|
$ /etc/init.d/init_disk.sh umount_flash_config |