Overview

Model: Back-UPS ES 750

Battery Details

SpecificationDetail
Image

PartAJC-D7S
Voltage12v
Capacity7Ah
Type

Sealed Lead Acid (AGM)

TerminalsF2
Length5.94 in / 150.9 mm
Width2.56 in / 65 mm
Height3.7 in / 94 mm
Weight4.5 lbs


Lithium Iron Phosphate Battery Replacement


I ordered this LiFePO4 battery off amazon which is the exact same size as the original.

...

I performed a capacity test on the old lead acid battery. The battery had a 3 Ah capacity when drained to 10.5v at 2A.


Shutdown Problem

I ended up having some quick shutdowns after replacing the battery.  

...

Testing the battery with a 10A load, the battery quickly dropped to 11.6V which the UPS would consider to be 0% left!

Solution

Two items were identified:

  • I was trying to pull more amperage than the replacement LiFePO4 battery would support. (Max 10A@12V or 1A@120V). Reduced number of protected devices on UPS.
  • Battery/UPS could be reset by using the Powerchute software. Marked the battery as replaced and ran a quick battery test.


Configuring the UPS

List Commands

Code Block
> upscmd -l  ups@localhost

Instant commands supported on UPS [ups]:

beeper.disable - Disable the UPS beeper
beeper.enable - Enable the UPS beeper
beeper.mute - Temporarily mute the UPS beeper
beeper.off - Obsolete (use beeper.disable or beeper.mute)
beeper.on - Obsolete (use beeper.enable)
load.off - Turn off the load immediately
load.off.delay - Turn off the load with a delay (seconds)
shutdown.reboot - Shut down the load briefly while rebooting the UPS
shutdown.stop - Stop a shutdown in progress
test.battery.start.deep - Start a deep battery test
test.battery.start.quick - Start a quick battery test
test.battery.stop - Stop the battery test
test.panel.start - Start testing the UPS panel
test.panel.stop - Stop a UPS panel test

...

Code Block
>upscmd ups@localhost beeper.offdisable
Username (root):          admin
Password: 
Unexpected response from upsd: ERR ACCESS-DENIED123456
OK

Test

Code Block
>upscmd ups@localhost test.battery.start.quick

>upscmd ups@localhost ups.test.result


Runtime Calibration


Please make sure that you have charged the batteries for 24 hours before doing this.


Runtime Calibration:
- Stop the APC software running on your computer and disconnect the USB cable.
- Remove all critical loads on your UPS and make sure that you have at least 30% load on it.
- Unplug the UPS from the power source and let it run On Battery until it discharges completely.
- Once the UPS is completely discharged, reconnect it back to the power source to recharge.
- Reconnect the load and cables back to the UPS and check the APC software for the runtime.


I just got my problem solved and very excited. Here are the steps i have taken:

1. Uninstalled APC PowerChute Personal Edition Version 2.2 downloaded from the site.
2. Managed to get hold of my previous APC PowerChute Personal Edition Version 1.3.1 for Windows 98/Me/2000/2003/XP that shipped with the UPS.
3. After the installation, I found the following option under Monitor System>Run Self Test:
To Help PowerChute to keep track of battery life, please click HERE when you replace battery on clicking it the following popup appeared Are you sure that you want to update your battery's replacement date now. On clicking, it instantly reported the estimated battery time as 45 Min!!!!.

Reseting 

I couldn't find anyway to do this. Marking the battery as replaces and running a quick test seems to be the only way.

Teardown

https://www.youtube.com/watch?v=6UerOTuV6R4


Circuit Board

Image Added